CVE-2023-4346: KNX Association KNX Protocol Connection Authorization Option 1 Overly Restrictive Account Lockout Mechanism
KNX Association KNX Protocol Connection Authorization Option 1 · listed in the CISA catalog of actively exploited vulnerabilities since 2026-07-15.
- CVSS v3.1 (CVE record)
- 7.5
- high
- EPSS (exploit probability, 30 days)
- 1.4%
- higher than 72.4% of all CVEs
- Added to CISA KEV
- 2026-07-15
- US federal due date 2026-07-29
- Automatable (CISA SSVC)
- yes
- technical impact: partial
What is CVE-2023-4346?
KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password.
If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.
CISA required action: Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk guidance and CISA’s “Forensics Triage Requirements”. Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.
CISA notes
Affected and fixed versions
From the CVE record published by the vendor or CVE numbering authority.
- KNX Association KNX Protocol Connection Authorization Option 1AffectedFixed in
- 0
not stated
| Product | Affected | Fixed in |
|---|---|---|
| KNX Association KNX Protocol Connection Authorization Option 1 |
| not stated |
How to fix it
- The CVE record names no fixed version – check CISA's required action for updates and mitigations.
- CISA's deadline for US federal agencies: 2026-07-29 (passed) – a useful benchmark for everyone else, too.
Workaround:
- The KNX Association recommends users always set the BCU Key in every KNX Project that is already finished and will be commissioned in the future.
- Handover the BCU Key as part of the Project Documentation to the Building Owner.
CISA's assessment (SSVC)
- Exploitation
- Exploited in the wild
- Automatable
- Yes – attackers can automate it at scale
- Technical impact
- Partial – limited control or information
Weakness: CWE-645 Overly Restrictive Account Lockout Mechanism
References
Government
Trackers and catalogs
Data: CISA Known Exploited Vulnerabilities (public domain) · CVE Program records incl. CISA ADP enrichment · OSV.dev (CC BY 4.0) incl. Ubuntu and Debian security data · FIRST EPSS · endoflife.date. Updated automatically – facts last changed 2026-11-21. Always confirm with the vendor's or distribution's advisory before patching.